Sistem de testare a imunității prin RF
Manual de utilizare
Aplicabil LISUN models: AB-EM
The AB-EM electromagnetic clamp complies with the national standard IEC 61000-4-6 and is a specialized product for testing the immunity of equipment to radio-frequency field-induced conducted disturbances.injecting disturbance signals into the cable assemblies in the slots so that the Equipment Under Test (EUT) is subjected to the levels specified in the national standard.
For precise measurements, the electromagnetic clamp is also equipped with an auxiliary absorption clamp and calibration pieces.
Categorii
See Tables 1 and 2 for the coupling coefficient and attenuation characteristic curves; the difference is 9.5 dB ± 1.5 dB.
Maximum input power: 100 W (5 minutes);
Injection frequency: 150 kHz to 230 MHz;
At frequencies greater than 10 MHz, the coupling/decoupling directivity is greater than 10 dB
Measurable cable diameter: <Φ18 mm
Atașamente
Instruction Manual 1 copy
Test Cable One
100W 6dB Attenuator One
Calibration Fixture (Optional) One set
Using Connection Diagrams
AB-EM

AB-EM Data Sheet
Serial No.: 21021 Differential Error: 9.5 dB ± 1.5 dB Date: April 29, 2021
| Frecventa (MHz) | Coupling Coefficient (dB) | Attenuation Coefficient (dB) | Difference (dB) |
| 0.15 | -2.7 | -12.3 | 9.6 |
| 0.2 | -2.4 | -12.0 | 9.6 |
| 0.3 | -2.2 | -11.8 | 9.6 |
| 0.32 | -2.2 | -11.8 | 9.6 |
| 0.35 | -2.2 | -11.8 | 9.6 |
| 0.4 | -2.1 | -11.8 | 9.7 |
| 0.45 | -2.1 | -11.8 | 9.7 |
| 0.5 | -2.1 | -11.8 | 9.7 |
| 0.55 | -2.1 | -11.8 | 9.7 |
| 0.6 | -2.1 | -11.8 | 9.7 |
| 0.65 | -2.1 | -11.8 | 9.7 |
| 0.74 | -2.1 | -11.8 | 9.7 |
| 0.75 | -2.1 | -11.8 | 9.7 |
| 0.8 | -2.2 | -11.9 | 9.7 |
| 0.85 | -2.3 | -11.9 | 9.6 |
| 0.9 | -2.4 | -12.1 | 9.7 |
| 0.95 | -2.5 | -12.1 | 9.6 |
| 1 | -2.5 | -12.1 | 9.6 |
| 1.5 | -2.1 | -11.7 | 9.6 |
| 2 | -2.1 | -11.7 | 9.6 |
| 2.5 | -2.1 | -11.7 | 9.6 |
| 3 | -2.1 | -11.7 | 9.6 |
| 4 | -2.2 | -11.8 | 9.6 |
| 5 | -2.2 | -11.8 | 9.6 |
| 6 | -2.3 | -11.8 | 9.5 |
| 7 | -2.4 | -11.8 | 9.4 |
| 8 | -2.4 | -11.8 | 9.4 |
| 9 | -2.5 | -11.9 | 9.4 |
| 10 | -2.6 | -11.9 | 9.3 |
| 12 | -2.8 | -12.1 | 9.3 |
| 15 | -3.2 | -12.4 | 9.2 |
| 18 | -3.5 | -12.6 | 9.1 |
| 20 | -3.6 | -12.8 | 9.2 |
| 22 | -3.6 | -12.8 | 9.2 |
| 25 | -3.5 | -12.8 | 9.3 |
| 28 | -3.1 | -12.4 | 9.3 |
| 30 | -2.6 | -11.9 | 9.3 |
| 32 | -2.2 | -11.5 | 9.3 |
| 35 | -1.3 | -10.6 | 9.3 |
| 38 | -0.5 | -9.8 | 9.3 |
| 40 | 0.0 | -9.3 | 9.3 |
| 45 | 1.1 | -8.4 | 9.5 |
| 50 | 1.8 | -7.8 | 9.6 |
| 60 | 2.5 | -7.4 | 9.9 |
| 70 | 2.6 | -7.1 | 9.7 |
| 80 | 2.7 | -6.9 | 9.6 |
| 85 | 2.9 | -6.9 | 9.8 |
| 90 | 3.0 | -6.9 | 9.9 |
| 95 | 3.2 | -6.9 | 10.1 |
| 100 | 3.3 | -6.8 | 10.1 |
| 120 | 3.5 | -6.8 | 10.3 |
| 140 | 3.4 | -7.0 | 10.4 |
| 160 | 2.6 | -8.0 | 10.6 |
| 180 | 1.9 | -8.2 | 10.1 |
| 200 | 0.9 | -9.3 | 10.2 |
| 210 | 0.6 | -9.6 | 10.2 |
| 220 | 0.1 | -10.1 | 10.2 |
| 230 | -0.1 | -10.3 | 10.2 |


List of AB-EM Calibration Fixtures
| Nu. | Model | Nume | Quantity/piece |
| 1 | M-004 | 150Ω/50Ω Adapter | 2 |
| 2 | M-006 | 5 W / 50 Ω load | 1 |
| 3 | E-001 | L-Shaped Calibration Bracket | 2 |
| 4 | E-003 | 4mm Test Rod (725mm) | 1 |
*The 4mm test probe is inside the electromagnetic clamp packaging box;
Soluție de testare pentru corpuri de iluminat LED și drivere de putere LED
Sistem goniofotometric: LSG-6000, LSG-1890B, LSG-1700
Spectroradiometru și sistem de testare a sferei integratoare: LPCE-2 or LPCE-3
LED Life menține un sistem de testare în conformitate cu LM-80: LEDLM-80PL
Test de impermeabilitate pentru nivelurile IPX5 și IPX6: JL-56
Mașină de testare a etanșeității la praf pentru testarea IP5X și IP6X: SC-015
Testere de drivere de putere LED: LS2090 (pentru laborator) și ATE-2 (pentru linia de producție)
Tester de siguranță electrică: LS9955
Soluție de testare CFL și balast electronic
Sistem goniofotometric: LSG-1890B or LSG-1700
Integrarea sistemului de testare cu sferă și spectrofotometru: LPCE-2 or LPCE-3
Balast de referință reglabil: DYJ-50Hz, HCS-109A și DYJ-HID
Tester de balast electric: WT5000 (pentru laborator) și ATE-1 (pentru linia de producție)
Torsometru digital și tester de durată de viață multidirecțională: CH338 și CH316
Testere de siguranță electrică: LS9923, ZRS-3H, ZY-3
Soluții de testare EMC și EMI pentru corpuri de iluminat CFL și LED
Sistem de testare EMI: EMI-9KB or EMI-9KA
Simulator de descărcare electrostatică: ESD61000-2
Măsurarea imunității EFT: EFT61000-4
Generator de supratensiune: SG61000-5
Generator de căderi de tensiune și întreruperi: CSS61000-11
Generator de unde inelare: RWG61000-12

www. Lisungroup.com
Brevete depuse
Toate drepturile rezervate de Lisun grup
Sub rezerva modificării fără notificare

中文简体